HartBR

Rocket-1 Single-Phase Recloser

Smart single-phase recloser that installs in a standard fuse cutout. 15.5kV and 27kV/38kV-M versions, 200A, vacuum interruption in a polymer body. Self-powered with no batteries, built-in GPS for fault location, IoT radio (LoRa/NB-IoT) for SCADA and Bluetooth app setup. Works as a single- or three-phase recloser, switch or sectionalizer. Tested to IEEE C37.60-2019.

Used in
Distribution / Electric Utility

No payment needed. We'll send pricing, availability and lead time.

Download datasheet (PDF, 1.5 MB)

Key specifications

Typesingle-phase recloser installed in a conventional fuse cutout; vacuum interruption, polymeric insulation (100% polymer body, 25-year life)
Operating modessingle-phase recloser, three-phase (synchronised with other Rocket-1 units), switch, sectionalizer; no extra licences
15.5 kV versionrated 13.8 kV, max 15.5 kV; BIL 110 kV; power frequency 50 kV dry (1 min) / 45 kV wet (10 s); breaking 4.2 kA / 1 s
27 kV / 38 kV-M versionrated 24 kV, max 27 kV; BIL 150 kV; power frequency 60 kV dry / 60 kV wet; breaking 6.3 kA / 1 s
Rated current200 A; rated frequency 50/60 Hz; minimum pickup 4 A
Metering accuracy (protection)±5% plus 50 mA for settings up to 200 A, ±10% above
Openings to lockout4 (configurable)
CommunicationLoRa / NB-IoT / Bluetooth 5.0; protocols LoRaWAN / DNP 3.0; SCADA integration with on-board radio and antenna
Powerself-powered by energy harvesting, no batteries; up to 5 days autonomy in the open position to receive remote commands
Featuresbistable magnetic actuator (no springs), embedded GPS for fault location, temperature/humidity and electric-field sensors, LED and mechanical (semaphore) status indicators
Hart Devices App (Android/iOS) via Bluetoothstatus, commands, event logs and configuration
Protection degreeIP65; standard IEEE C37.60-2019 (tested at CESI, Italy)

From the manufacturer's datasheet. Ratings vary by model, so our engineers confirm the exact specification with your quotation.