ESIT

Current and Potential Transformers

Indoor and outdoor CTs and PTs, 7.2kV to 36kV. Cast resin current transformers (CTM, CTB, CTD and CTSG for indoor; CTH for outdoor) and voltage transformers (VTM, VTB and VTBF for indoor; VTH and 2VTH for outdoor), plus oil-type CTY and VTY for 36kV outdoor. Outdoor CTH available in 15kV - 26kV with ERC Sticker and test report. Also low-voltage toroidal and ring-type CTs.

Used in
GenerationSubstationDistribution / Electric UtilityEnd-Users / Consumers
Applications
MV Switchgear

No payment needed. We'll send pricing, availability and lead time.

Download datasheet (PDF, 9.7 MB)

Key specifications

Indoor CTsCTM (narrow type), CTB (block type), CTB Barrier, CTD (busbar type) 7.2-24 kV, CTSG (bushing type) 17.5-36 kV
Outdoor CTsCTH 10/20/30 cast resin (6.3-36 kV); CTY 30 oil type (36 kV)
Indoor VTsVTM, 2VTM (double pole), VTB, VTBF / 2VTBF (with fuse); Outdoor VTs: VTH, 2VTH (double pole), VTY 30 oil type (36 kV)
Voltage classes7.2-12 kV (20-28 kV / 60-75 kV), 17.5-24 kV (38-50 kV / 95-125 kV), 36 kV (70 kV / 170 kV) power-frequency / impulse
VT primary3.3-11/√3 kV, 15-22/√3 kV, 30-36/√3 kV (single pole); 3.3-11, 15-22, 30-36 kV (double pole)
Outdoor CTH 20 as supplied by Montrelec15 kV in a 24 kV mold; ratio up to 1500 A; 1 A or 5 A; class 0.3; 15 VA; rating factor 2; Fs5; BIL 95 kV; creepage 720 mm
CT optionsdual ratio, multi ratio (4 ratios), extended range (1-150%); Ith up to 60 kA 1 s
Supplied with ERC sticker and test report; re-tested with OMICRON analyzer before delivery
Alsolow-voltage toroidal and ring-type CTs (0.72 kV), post insulators and wall bushings
StandardsIEC, VDE, ANSI (CTH 20: ANSI/IEEE C57.13, IEC 60044-1)

From the manufacturer's datasheet. Ratings vary by model, so our engineers confirm the exact specification with your quotation.