Thytronic

Differential Protection Relay

The XMR-T relay, part of the XMORE platform, provides complete protection for two- or three-winding transformers in medium voltage applications.

Used in
GenerationSubstationEnd-Users / Consumers
Applications
MV Switchgear

No payment needed. We'll send pricing, availability and lead time.

Download datasheet (PDF, 2.5 MB)

Key specifications

Application2- or 3-winding transformer protection (MV)
Protection functions87T, 64REF, 87NHIZ, 50/51, 50N/51N, 67N, 46, 49, 37, 24, 27, 59, 59N, 81O/81U, BF, 74CT, 74TCS; 26 and 86 with optional modules
87Tdouble-slope biased differential with 2nd harmonic restraint
Current inputs11 phase + 1 residual, 1 A or 5 A (with external analog input module)
Binary inputs7–53; output relays: 7–31 (8 A)
Auxiliary supply (nominal)24–110 Vac/Vdc or 110–230 Vac/Vdc
ProtocolsIEC 61850 Ed.2, Modbus RTU/TCP, IEC 60870-5-103, DNP3
Redundancy/time syncHSR, PRP, RSTP; SNTP, IEC 1588
Rated frequency50/60 Hz

From the manufacturer's datasheet. Ratings vary by model, so our engineers confirm the exact specification with your quotation.