SOJO

Solid Insulated Vacuum Recloser

SVR is KEMA type tested and designed for use on overhead distribution lines as well as distribution substation application for all voltage levels up to 15.5kV , 27kV and 38kV.

Used in
SubstationDistribution / Electric Utility

No payment needed. We'll send pricing, availability and lead time.

Download datasheet (PDF, 15.6 MB)

Key specifications

Rated voltage15.5 / 27 / 38 kV; 50/60 Hz
Rated current630/800 A
Short-circuit breaking16 kA (15.5 kV), 12.5/16 kA (27 kV), 12.5 kA (38 kV)
Short-time withstand16 kA/3 s (15.5 kV), 12.5 or 16 kA/3 s (27 kV), 12.5 kA/3 s (38 kV)
Power-frequency withstand (1 min dry)50 / 60-70 / 70 kV
BIL125 / 125-150 / 170 kV
Operating sequenceO-0.2s-CO-2s-CO-2s-CO (max 4 trips)
Mechanical endurance10,000 ops; magnetic actuator; SF6 free
Sensors3 encapsulated CTs (±0.2%), up to 6 voltage sensors (±5%)
ControllerSJFD2000 (IEC 61850; other brands compatible)
IP67; pollution class IV very heavy; -40 to +55 °C
StandardsIEC 62271-111:2019, IEEE C37.60; KEMA type tested

From the manufacturer's datasheet. Ratings vary by model, so our engineers confirm the exact specification with your quotation.