Montrelec

ATS Controller

Intelligent dual-source ATS controller for all types of transfer switches: Breakers, Solenoid, Contactor and Change Over Switches. Monitors both sources (3-phase voltage, frequency and phase sequence), with genset start/stop, scheduled test runs, load shedding, event log and RS485 Modbus remote monitoring. LCD display, panel mounting, IP55 with gasket.

Used in
End-Users / Consumers
Applications
Transfer Switches

No payment needed. We'll send pricing, availability and lead time.

Datasheet available on request. Mention it in your quote notes.

Key specifications

UsePC three-stage and two-stage, CB (breaker) and CC (contactor) transfer switches; also stored-energy ATS
System typesmains & mains, mains & generator, generator & mains, generator & generator; 2 isolated neutrals supported
Measuresboth sources' 3-phase L-N/L-L voltage, frequency and phase; current, kW, kvar, kVA, PF, kWh/kvarh energy, close counts, supply time
Protectionover/under voltage, loss of phase, reverse phase sequence, over/under frequency; separate over-current warning/trip per source
Functionsauto/manual, auto re-closing, sync transfer (voltage/frequency/phase difference), phase sequence transfer, load shedding of 3 non-essential loads
Generator controlremote start/stop, scheduled run / not run (daily, weekly, monthly, with or without load), 2-generator cycle, master or balance run
SupplyDC 8–35V continuous (AC 90–280V on AC-supplied versions); <5W (standby ≤2W)
AC input3P4W/3P3W/2P3W 80–625V L-L; 1P2W 50–360V L-N; 50/60Hz
I/Oclose relays 16A AC250V volt-free; auxiliary relays 16A/7A AC250V; digital inputs active to ground
Communicationisolated RS485, Modbus RTU (address 1–254, 2400–19200 bps)
Display & case132x64 backlit LCD, 99-event log, real-time clock, passwords; 197 x 152 x 47 mm, cutout 186 x 141 mm, about 0.8 kg; IP55 with gasket; -25 to +70°C, 20–93% RH

From the manufacturer's datasheet. Ratings vary by model, so our engineers confirm the exact specification with your quotation.