Contactplasma

CKM Transfer Switch

Motor-driven change-over switch. Current Ratings from 125A-1600A. Available in 3, 4, 6 or 8 poles. Rated insulation voltage 1000V AC, operational ratings up to 690V AC. Motor 220-240V AC (24V DC on request), change-over time 4-5 s, with manual handle operation.

Used in
End-Users / Consumers
Applications
Transfer Switches

No payment needed. We'll send pricing, availability and lead time.

Datasheet available on request. Mention it in your quote notes.

Key specifications

TypeMotor-driven one-case change-over switch, positions I-0-II (DKM = motorised deviator II-I version)
Rated current Ith (40C, free air)125, 160, 200, 250, 400, 630, 800, 1000, 1250, 1600A
Poles3, 4, 6 or 8
Rated insulation voltage Ui1000VAC / 600VDC; impulse withstand 8kV (125-630A), 12kV (800-1600A)
Operational current AC21/AC22 at 690Vequal to rated current (125-1600A); AC23 at 500V: 125-1600A; AC23 at 690V: 63-500A
Short-time withstand Icw (1s)8kA (125A) to 35kA (1250-1600A); making capacity Icm 14-73.5kA peak
Motor operator supply220-240VAC 50/60Hz standard; 24VDC on request; version CKM\S complete with electronic control card
Change-over time I-0-II4s (125-630A), 5s (800-1600A); manual handle operation possible on supply failure
Mechanical endurance8000 ops (125-250A), 5000 (400-630A), 3000 (800-1600A)
Constructionself-extinguishing anti-track polyester case, silver-plated copper contacts, padlockable (up to 3 padlocks); 4P neutral makes before / breaks after phases
StandardsIEC/EN 60947-3; tropicalised per IEC 60068-2

From the manufacturer's datasheet. Ratings vary by model, so our engineers confirm the exact specification with your quotation.